new products will be listed--SA2200 Power Quality Analyzer

Key Feature
1 to 100th harmonic and 99th inter-harmonic display
Sample rate can reach to 200kS/s
GPS/Beidou time synchronization 
WIFI, LAN and USB Host communication

Input           *Note: measured on Reference Voltage Input A/L1.

     Voltage Input
Input Channels
4 (3 phase + neutral) DC coupling
Max continuous input voltage
(AC+DC)1000Vrms
Accuracy
±0.1% of nominal voltage
Max pulse peak voltage
6kV
Input impedance
4MΩ
Current Input
Input Channels
4 (3 phase + neutral) DC coupling
Type
Clamp Current Sensor, with mV output
Input range
0~6000A
Input impedance
100kΩ
Arms(AC)
10mV/A
1mV/A
65mV/1000A

0~100A 
1~1000A
15~6000A
Sampling  
Resolution
8 channels 16 bits ADC, sample synchronously
Sampling rate
Max 200kS/s
Measurement

Measurement range
Resolution
Accuracy
Frequency
50Hz
42.50~57.50 Hz
0.001Hz
±0.01Hz
60Hz
51.00~69.00 Hz
0.001Hz
±0.01Hz
400Hz
385-414 Hz
0.01Hz
±0.1Hz
Harmonic
Harmonic number
Interharmonic
Harmonic voltage
Harmonic current
THD
DC relative
Frequency
Phase
1~100
1~99
0.0~100.0%
0.0~100.0%
0.0~100.0%
0.0~100.0%
0~6000Hz
-360°~ 0°


0.1%
0.1%
0.1%
0.1%
1Hz


±0.1%±n×0.1%
±0.1%±n×0.1%
±2.5%
±0.2%
1Hz
±n×1.5°

General Characteristics

     Display
Screen
Color TFT LCD
Size
5.6 inch
Resolution
640X480
Brightness
Adjustable

Power
Adapter input
AC  100-240V  50/60Hz
Adapter output
DC  12V  2A
Battery
Lithium ion battery     7.4V  5.2Ah
Battery operating time
>6 hours
Battery charge time
5 hours

  